Fluke 1662 Multifunction Testers
Essential testing power with trusted Fluke reliability
Product Overview
Fluke 1662 Multifunction Tester Price in Bangladesh
Fluke 1662 Multifunction Tester is a rugged and dependable tool built for everyday electrical testing, allowing you to explore the Fluke 1662 Multifunction Tester Price in Bangladesh as a practical solution for installation verification. Designed for professionals, this tester delivers reliable performance with all the essential features required for routine electrical diagnostics.
This multifunction tester provides a comprehensive range of testing capabilities including voltage, frequency, insulation resistance, loop and line impedance, and continuity testing. It also supports RCD testing with automatic sequences, helping electricians perform safety checks efficiently and accurately. These features make it suitable for ensuring compliance with electrical standards in various environments.
The device is known for its simplicity and ease of use. With an intuitive interface and clearly arranged controls, users can quickly access different testing modes without confusion. Its compact design and portable structure make it convenient for on site work, while the included accessories enhance usability for a wide range of testing scenarios.
Durability is one of the key strengths of this tester. Built with high quality materials, it is designed to withstand demanding job site conditions and long term use. The robust construction ensures consistent performance, even in challenging environments where reliability is critical.
In addition to its durability, the tester offers practical features such as polarity checking and fault current calculation, which help users identify potential electrical issues quickly. These capabilities improve efficiency and reduce the time required for troubleshooting and installation verification.
Overall, this multifunction tester is a solid choice for professionals who need a reliable and straightforward testing device. Its combination of essential features, user friendly design, and dependable performance makes it a valuable tool for electrical maintenance, inspection, and installation tasks.
Key Features: Fluke 1662 Multifunction Testers
A solid, reliable, basic installation tester
- Tests voltage and frequency
- Checks wiring polarity to detect broken N wires
- Measures insulation resistance and loop and line resistance
- Measures motor windings with continuity test
- Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
Specifications
Specifications: Fluke 1662 Multifunction Testers
| AC voltage measurement | ||
| Range | 500 V | |
| Resolution | 0.1 V | |
| Accuracy 45 Hz – 66 Hz | 0.8% + 3 | |
| Input impedance | 360 kΩ | |
| Overload protection | 660 V rms | |
| Continuity testing (RLO) | ||
| Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω | |
| Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
| Open Circuit Voltage | >4 V | |
| Insulation resistance measurement (RISO) | ||
| Accuracy of tTest voltage (at rated test current) | +10%, -0% | |
| Test voltage | 100 V 250 V 500 V 1000 V |
|
| Insulation resistance range | 20 MΩ / 50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ |
|
| Resolution | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ |
|
| Test current | 1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ |
|
| Loop and line impedance (ZI) | ||
| Range | 10 Ω / 0.001 Ω / High current mΩ mode | |
| Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
| Prospective earth fault current, PSC test | ||
| Range | 1000 A / 10 kA (50 kA) | |
| Resolution | 1 A / 0.1 kA | |
| Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
| RCD testing, RCD types tested | ||
| RCD Type | A4, AC¹, G², S³ | |
| Notes | ¹Responds to AC ²General, no delay ³Time delay 4Responds to pulsed signal 5Responds to smooth DC signal |
|
| Tripping speed test (ΔT) | ||
| Current settings¹ | 10-30-100-300-500-1000 mA – VAR 10-30-100 mA |
|
| Multiplier | x ½, x 1 x 5 |
|
| Measurement range | RCD Type G | 310 ms 50 ms |
| RCD Type S | 510 ms 160 ms |
|
| Notes | ¹1000 mA type AC only 700 mA maximum type A in VAR mode VAR mode not available for type B. |
|
| RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) | ||
| Current range | 30% to 110% of RCD rated current¹ | |
| Step size | 10% of IΔN² | |
| Dwell time | Type G | 300 ms/step |
| Type S | 500 ms/step | |
| Measurement accuracy | ±5% | |
| Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (≤10 mA) 50% to 200% for Type B ²5% for Type B |
|
| Notes | ¹30% to 150% for Type A IΔN > 10 mA 30% to 210% for Type A IΔN = 10 mA 20% to 210% for Type B |
|
| Phase Sequence Indication | ||
| Icon | ||
| General Specifications | ||
| Size (L x W x H) | 10 x 25 x 12.5 cm | |
| Weight (incl. batteries) | 1.3 Kg | |
| Battery size, quantity | Type AA, 6 ea. | |
| Sealing | IP-40 | |
| Safety | Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition | |
| Overvoltage | CAT III / 500V; CAT IV 300V | |
| Performance | EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition | |